Heat loss & insulation calculator

Work out U-values layer by layer, a room's heat loss, the yearly heating cost, what insulation saves and how thick it needs to be.

List the layers from inside to outside. The order changes the temperature picture, not the U-value.

    The temperature picture needs a browser that can draw.

    How to use

    1. U-value: build the wall, roof or floor layer by layer: pick each material and its thickness. The U-value (lower is better) and a picture of the temperature through it update as you go.
    2. Room heat loss: type the area and U-value of each part of a room, its volume and how leaky it is, and the coldest outside temperature you plan for.
    3. Yearly cost & savings: use the room's heat loss coefficient with your local degree-days and energy price, and see what an upgrade saves and how fast it pays back.
    4. Insulation thickness: see how thick each insulation needs to be to reach a target U-value.

    Keyboard and touch

    Enter in a boxWork out the result
    TabMove through materials, thicknesses and buttons

    Tips

    • Halving the U-value halves the heat loss through that part. Going from nothing to some insulation saves far more than adding more to an already insulated wall.
    • Windows often lose more heat per square metre than anything else; check them in Room heat loss.
    • Air changes matter: an old draughty house can have 1.5 or more per hour, a new airtight one 0.3 to 0.5. Keep enough fresh air for health.
    • US R-values are the metric R-value × 5.678. R-13 batts are about R 2.3 m²K/W.
    • Timber studs, steel ties and other "thermal bridges" make real walls a little worse than the layer sum shown here.
    • Inside surfaces colder than the room's dew point get condensation; the temperature picture shows how cold the inner surface is.

    About this calculator

    The U-value follows the simple layer method of ISO 6946: each layer's R = thickness ÷ thermal conductivity, plus inside and outside surface resistances (0.13 and 0.04 m²K/W for walls, 0.10 and 0.04 for heat flowing up, 0.17 and 0.04 for heat flowing down) and 0.18 m²K/W for a still air gap. It does not correct for thermal bridges, wall ties, fixings or gaps in the insulation. Conductivities are typical values (ISO 10456, CIBSE Guide A); real products differ, so use the value on the product's data sheet.

    Ventilation heat loss is 0.33 × air changes per hour × volume (W/K), from the density and heat capacity of air. Yearly heat is heat loss coefficient × degree-days × 24 h; this ignores sun, people and appliances, which lower real bills. This is an estimate for learning and comparing options, not a heating-system design or a building-regulations calculation.