Air changes per hour from room size, fans and air cleaners; airflow for a target; clearing times; CO2 from people and ventilation; and the ASHRAE 62.2 home formula.
This is the dwelling-unit formula from ASHRAE Standard 62.2 (Qtot = 0.03 × floor area + 7.5 × (bedrooms + 1)). Building codes adopt it with their own credits and exceptions: your local code and a qualified installer decide what is required.
| Arrow keys on the tabs | Change calculator |
|---|---|
| Typing | Results update at once |
Air changes per hour = airflow ÷ room volume. Clearing times assume perfect mixing: the share removed after t hours is 1 − e^(−ACH × t), the relation behind the commonly published "air changes and removal time" tables. Steady-state CO2 = outdoor + CO2 generation ÷ outdoor air flow, the mass balance used in ASTM D6245; it only holds once the level has stopped changing. The whole-house figure uses the ASHRAE 62.2 formula. Estimates only: not a design, code or health check. Nothing is sent anywhere.